How To Set Thermostat Honeywell
Honeywell Pro Series Thermostat
Honeywell Pro Series ThermostatModel : T6 Pro
Other Honeywell Pro Thermostat Manuals:
- T4 Pro
- T6 Pro
- RTH5160 Not-Programmable Thermostat
- WiFi Touchscreen Thermostat Installation Manual
- WiFi Color Touchscreen Thermostat
- VisionPRO WiFi Thermostat
Bundle Includes
- T6 Pro Thermostat
- UWP Mounting System
- Honeywell Standard Installation Adapter (J-box adapter)
- Honeywell Decorative Cover Plate –Small; size 4-49/64 in ten 4-49/64 in x11/32 in (121 mm 10 121 mm x 9 mm)
- Screws and anchors
- 2 AA Batteries
- Installation Instructions and User Guide
Optional Comprehend Plate installation
NOTE: If Optional Embrace Plate is non required, see "UWP Mounting Organisation installation" on next page.
Apply the Optional Cover Plate when:
- Mounting the thermostat to an electric junction box
- Or when you need to cover pigment gap from quondam thermostat.
- Dissever the Junction Box Adapter from the Embrace Plate. See Effigy 1.
- Mount the Junction Box Adapter to the wall or an electrical box using whatsoever of the eight spiral holes. Insert and tighten mounting screws supplied with Cover Plate Kit. Do not overtighten. See Figure ii. Make sure the Adapter Plate is level.
- Attach the UWP by hanging it on the meridian hook of the Junction Box Adapter so snapping the bottom of the UWP in place. Run into Figure three.
- Snap the Cover Plate onto the Junction Box Adapter. Run into Figure 4.
UWP Mounting System installation - Before starting, turn the power off at the breaker box or switch. Open package to find the UWP. See Figure 5.
- Position the UWP on wall. Level and marking pigsty positions. See Figure 6. Drill holes at marked positions, and and so lightly tap supplied wall anchors into the wall using a hammer.
Drill seven/32" holes for drywall.
- Pull the door open and insert the wires through wiring hole of the UWP. Run across Figure 7.
- Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP no longer moves. Close the door. See Figure 8.
Ability options
Insert R and C wires into designated terminals for primary Air conditioning ability (C terminal is optional if batteries are installed, only information technology is recommended). Remove wires by depressing the terminal tabs.
Insert AA batteries for primary or backup power.
Setting Slider Tabs
Fix R Slider Tab
- Use congenital-in jumper (R Slider Tab) to differentiate between one or two transformer systems.
- If there is just i R wire, and it is connected to the R, Rc, or RH terminal, set up the slider to the upwardly position (1 wire).
- If there is one wire connected to the R terminal and i wire connected to the Rc terminal, prepare the slider to the down position (2 wires).
NOTE: Slider Tabs for U terminals should be left in identify for T6 Pro models.
Wiring terminal designations
Note: Not all terminals may be used, depending on the system type that is being wired. The most unremarkably used terminals are shaded.
- Terminal tin can be jumped using Slider Tab. See "Setting Slider Tabs" in a higher place.
- The THP9045A1023 Wire Saver Module is used on estrus/cool systems when you lot only have iv wires at the thermostat, and you need a 5th wire for a mutual wire. Use the K terminal in identify of the Y and G terminals on conventional or estrus pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more data.
Wiring conventional systems: forced air and hydronics
Shaded areas below use only to TH6320U/TH6220U or as otherwise noted.
- 1H/1C System (i transformer)
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [two]
- Y Compressor contactor
- C 24VAC mutual [three]
- W Heat relay
- G Fan relay
Oestrus-only Organization
- R Power [1]
- Rc [R+Rc joined past Slider Tab] [2]
- C 24VAC common [three]
- W Heat relay
Oestrus-only System (Series twenty) [5]
- R Series xx valve terminal "R" [1]
- Rc [R+Rc joined past Slider Tab] [2]
- Y Series xx valve terminal "W"
- C 24VAC common [3]
- West Series 20 valve terminal "B"
Heat-but System (power open zone valve) [5]
- R Power [i]
- Rc [R+Rc joined past Slider Tab] [2]
- West Valve
- C 24VAC common [three]
1H/1C System (two transformers)
- R Ability (heating transformer) [1]
- Rc Power (cooling transformer) [i]
- Y Compressor contactor
- C 24VAC common [3, 4]
- W Heat relay
- G Fan relay
Heat-merely System with Fan
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- C 24VAC mutual [three]
- W Heat relay
- Grand Fan relay
Cool-only Organisation
- R Ability [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [3]
- G Fan relay
2H/2C Arrangement (1 transformer) [six]
- R Ability [1]
- Rc [R+Rc joined by Slider Tab] [two]
- Y Compressor contactor (stage 1)
- C 24VAC common [3]
- W Heat relay (stage ane)
- Chiliad Fan relay
- W2 Oestrus relay (stage 2)
- Y2 Compressor contactor (phase ii)
NOTES
Wire specifications: Apply 18- to 22-gauge thermostat wire. Shielded cable is not required.
- Power supply. Provide disconnect ways and overload protection every bit required.
- Move R-Slider Tab on UWP to the R setting. For more data, meet "Setting Slider Tabs" on folio three
- Optional 24VAC common connection.
- Common connectedness must come from cooling transformer.
- In ISU prepare Heat system type to Radiant Oestrus. Set number of cool stages to 0.
- In Installer Setup, gear up arrangement type to 2Heat/2Cool Conventional
Wiring oestrus pump systems
Shaded areas below utilise only to TH6320U/TH6220U or equally otherwise noted.
- 1H/1C Heat Pump System
- R Power [1]
- Rc [R+Rc joined past Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [iii]
- O/B Changeover valve [7]
- G Fan relay
2H/1C Rut Pump Arrangement [8]
- R Power [1]
- Rc [R+Rc joined past Slider Tab] [ii]
- Y Compressor contactor
- C 24VAC mutual [3]
- O/B Changeover valve [7]
- G Fan relay
- Aux Auxiliary heat
- East Emergency heat relay
- L Oestrus pump fault input
2H/2C Heat Pump System [nine]
- R Ability [i]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor (phase ane)
- C 24VAC common [3]
- O/B Changeover valve [seven]
- G Fan relay
- Y2 Compressor contactor (stage two)
- L Heat pump fault input
3H/2C Heat Pump Organisation (TH6320U only) [10]
- R Power [1]
- Rc [R+Rc joined past Slider Tab] [2]
- Y Compressor contactor (phase 1)
- C 24VAC mutual [iii]
- O/B Changeover valve [7]
- Grand Fan relay
- Aux Auxiliary heat
- E Emergency estrus relay
- Y2 Compressor contactor (stage 2)
- L Heat pump fault input
Dual Fuel System
- R Power [i]
- Rc [R+Rc joined past Slider Tab] [2]
- Y Compressor contactor (phase 1)
- C 24VAC common [iii]
- O/B Changeover valve [7]
- G Fan relay
- Aux Auxiliary oestrus
- East Emergency heat relay
- Y2 Compressor contactor (stage ii – if needed)
- L Heat pump mistake input
- S Outdoor sensor
- S Outdoor sensor
NOTES
Wire specifications: Utilise xviii- to 22-gauge thermostat wire. Shielded cable is not required.
- Power supply. Provide disconnect ways and overload protection every bit required.
- Move R-Slider Tab on UWP to the R setting. For more information, encounter "Setting Slider Tabs" on page 3
- Optional 24VAC common connection.
- In Installer Setup, set arrangement type to 2Heat/2Cool Conventional.
- In Installer Setup, fix changeover valve to O (for cool changeover) or B (for estrus changeover).
- In ISU set Heat system blazon to Estrus pump. 1 compressor and 1 phase of backup heat.
- In ISU set Heat organization type to Heat pump. 2 compressors and 0 stage of backup heat.
- In ISU set Estrus system type to Estrus pump. 2 compressors and 1 stage of backup estrus.
Thermostat mounting
- Push excess wire back into the wall opening.
- Shut the UWP door. It should remain closed without bulging.
- Align the UWP with the thermostat, and button gently until the thermostat snaps in place.
- Turn the power on at the billow box or switch.
Organisation operation settings
- Press the Mode push to cycle to the next available Arrangement fashion.
- Cycle through the modes until the required System mode is displayed and leave information technology to activate.
Note: Available System modes vary by model and system settings.
System modes:
- Auto
- Heat
- Cool
- Em Estrus
- Off
Fan operation settings
- Press the Fan button to cycle to the next bachelor Fan way.
- Bike through the modes until the required Fan mode is displayed and leave it to actuate.
NOTE: Bachelor Fan modes vary with system settings.
Fan modes:
- Auto: Fan runs only when the heating or cooling arrangement is on.
- On: Fan is always on.
- Circ: Fan runs randomly near 33% of the fourth dimension.
Installer setup (ISU)
- Press and concur CENTER and + buttons for approximately 3 seconds to enter avant-garde card.
- Press Select to enter ISU.
- Press Select to bicycle through menu setup options.
- Press + or – to alter values or select from available options.
- Press Select and confirm your settings or printing Back to ignore changes and render to ISU bill of fare screen to continue editing some other setup option.
- To stop setup process and relieve your setting, press Home and return to Home screen.
NOTE: A consummate list of all setup (ISU) parameters and options starts below and continues through page 10.
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
Installer system test
To perform a Organization Test:
- Press and concord Center and + buttons for approximately 3 seconds to enter advanced carte.
- Use + to go to Examination. Press Select to enter Organization Test.
- Apply + to change between Heat, Cool, Fan, Em Heat, or Ver (thermostat version information). Press Select.
- Printing + to turn stages on i at a time, and press – to plough them off.
- Utilize the Home push to exit the Arrangement Test.
System test System status
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
Default security lawmaking
The default security code for the Honeywell Pro Series thermostat is 1234
Heat
0 All Off
1 Heat Stage ane on
2 Rut Phase 2 also on
3 Rut Stage three besides on
Cool
0 All Off
1 Cool Phase 1 on
2 Cool Stage 2 also on
Em Heat
0 All Off
1 Em Rut on
Fan
0 Fan Off
1 Fan On
Specifications
Temperature Ranges
Heat: twoscore °F to 90 °F (4.5 °C to 32.0 °C)
Cool: 50 °F to 99 °F (ten.0 °C to 37.0 °C)
Working Ambience Temperature
32 °F to 120 °F (0 C° to 48.9 °C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.ix °C)
Shipping Temperature
-20 °F to 120 °F (-28.nine °C to 48.ix °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H 10 W x D)
4-one/xvi" H x iv-i/sixteen" W x one-5/32" D
103.5 mm H ten 103.v mm W 10 29 mm D
Electrical Ratings
CAUTION: ELECTRICAL Hazard
Can cause electrical stupor or equipment damage. Disconnect power before
beginning installation.
CAUTION: EQUIPMENT DAMAGE Hazard
Compressor protection is bypassed during testing. To prevent equipment damage, avert cycling the compressor speedily.
CAUTION: MERCURY Find
If this product is replacing a control that contains mercury in a sealed tube, do non place the erstwhile control in the trash. Contact your local waste management dominance for instructions regarding recycling and proper disposal.
Pull to remove the thermostat from the UWP
Client help
For assistance with this production, please visit customer.honeywell.com
Or call Honeywell Customer Care toll-complimentary at
ane-800-468-1502.
Automation and Command Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark.
© 2022 Honeywell International Inc.
33-00181EFS—01 M.S. 06-16
Printed in U.S.A.
Printed in U.S.A.
Source: https://manuals.plus/honeywell/honeywell-pro-series-thermostat-manual

0 Response to "How To Set Thermostat Honeywell"
Post a Comment